Vesi TS International Co., Ltd.
+8615809208763

Installation requirements for water softening equipment

Dec 28, 2021

1. The foundation shall be horizontal, and floor drain or drainage ditch shall be set nearby to drain the reclaimed wastewater. An independent power socket shall be set near the equipment


2. The salt tank shall be close to the exchange tank, and the shorter the salt suction pipe, the better.


3. Y-type filter and water meter shall be installed on the water inlet pipe, and sampling port shall be set at the water outlet.


4. Manual valves shall be installed on the water inlet and outlet pipes, and bypass valves shall be set between the water inlet and outlet to continue the water supply during regeneration or maintenance.


5. If the water pressure at the inlet is lower than 0.2MPa, an automatic booster pump shall be added.


6. The salt in the salt tank shall be industrial salt, and iodized salt and calcium salt shall not be added. In order to ensure that the salt solution concentration in the salt tank can reach saturation, first ensure that the dissolution time is not less than 6 hours, and forcibly regenerate once before the first use.


7. When the hardness of raw water is > 6mmol / L, grade 1-2 selection shall be increased.


8. The pipeline must be flushed before use to avoid impurities blocking the valve body and polluting the resin.


 Installation requirements for water softening equipment